Estimates indoor humidity from outdoor weather and the thermostat setting, and the moisture content wood flooring will trend toward. Works for heating and cooling season.
When outdoor air comes inside, the amount of water in it stays the same — only its temperature changes. Warm air can hold more water than cold air, so heating winter air makes the RH drop, and cooling summer air makes it rise.
Indoor RH = Outdoor RH × (Psat at outdoor temp ÷ Psat at indoor temp)
Saturation pressure (Psat) is calculated with the Magnus formula (over ice below freezing). Wood EMC uses the Hailwood–Horrobin model (Simpson), the same basis as the EMC Gauge.
Worst case: the result assumes no humidifier, no dehumidification by the AC, and no moisture from cooking, showers or occupants. Use it to estimate conditions when nobody was measuring — then verify with a hygrometer on site.